Introduction
1. Application
l Carbon dioxide lasers for cladding, welding and cutting
l Solid-state lasers for marking and 3D printing
l Semiconductor lasers for cladding, welding and cutting
l Fiber lasers for cladding, welding and cutting
2. Functions and Features
l Circulating pump made from stainless steel features large flow, high head, low noise and long service life. Besides, such components as water tank, pipeline and cooling valves are also made from stainless steel.
l The control system adopts a controller with Chinese/English (switchable) LCD and fully automatic CPU, making it visual and easy-to-operate. Water temperature precision can reach ±1℃. In addition, the controller featuring automatic fault diagnosis can display fault points on the screen, hence reminding the user of rapid processing.
l RS485 communication interface is added to implement communication function.
l It serves multiple functions with passive alarm and remote control terminals, making it easy to realize centralized control and monitoring of CNC.
l Dual-temp precision water chillers can cool laser and mirror plane simultaneously, which are the optimal choice for lasers.
II. Specification
Item \ Model | MCWL-15 | MCWL-25 | MCWL-35 | MCWL-50 | MCWL-70 | MCWL-100 | MCWL-120 | MCWL-150 | |||||
Cooling capacity | kW | 1.5 | 2.5 | 3.5 | 5.0 | 7.0 | 10.0 | 12.0 | 15.0 | ||||
kcal/h | 1300 | 2150 | 3000 | 4300 | 6000 | 8600 | 10300 | 12900 | |||||
Power supply | V,Hz | 380,3~,50 | |||||||||||
Rated power | kW | 0.94 | 1.8 | 2.2 | 2.9 | 3.3 | 5.3 | 5.3 | 5.6 | ||||
Rated current | A | 3.2 | 4.8 | 6.1 | 6.3 | 6.7 | 10.2 | 10.2 | 11.5 | ||||
Flow of low-temp. water pump | L/min | 10 | 16 | 16 | 25 | 25 | 40 | 45 | 50 | ||||
Head of low-temp. water pum | m | 25 | 45 | ||||||||||
Flow of high-temp. water pump | L/min | —— | —— | —— | —— | —— | —— | —— | —— | ||||
Head of high-temp. water pump | m | —— | |||||||||||
Water temp. range | ℃ | Fixed temp.: 15~50℃; low-temp water control precision ±1℃ | |||||||||||
Circulating water |
| Deionized water or purified water for drinking | |||||||||||
Ambient temp. | ℃ | 5~45℃ | |||||||||||
Noise | dB(A) | 58 | 62 | 62 | 62 | 68 | 72 | 72 | 75 | ||||
IP Code |
| IP44 | |||||||||||
Interface size (low-temp. water) | Water outlet G | 3/8″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 1″ | 1″ | 1″ | ||||
Water inlet G | 3/8″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 1″ | 1″ | 1″ | |||||
Interface size (high-temp. water) | Water outlet G | —— | —— | —— | —— | —— | —— | —— | —— | ||||
Water inlet G | —— | —— | —— | —— | —— | —— | —— | —— | |||||
Boundary dimension | mm | 400× | 520× | 520× | 670× | 670× | 780× | 780× | 750× | ||||
Water tank volume (effective) | L | 15 | 30 | 30 | 35 | 60 | 140 | 140 | 140 | ||||
Weight | kg | 70 | 90 | 120 | 140 | 160 | 280 | 280 | 300 |